Category
|
Description
|
Hazard
|
Standard
|
Corrective Action
|
VIEW
|
Scaffolds |
Employee on top of wall w/o fall protection. Fall hazard of about 22 feet to concrete floor below.
|
Fall Protection |
1926.501(b)(1)
1926.451(g)(1).
|
Employer needs to provide a safe work platform or fall protection system. Reference 1926.502 for Fall protection systems and criteria and practices.
|
VIEW
|
Scaffolds |
Inadequate scaffold foundation.
|
Fall Protection |
1926.451(c)(2)
|
Scaffold poles, legs, posts, frames, and uprights were not placed on base plates and mud sills or other adequate firm foundations |
VIEW
|
Scaffolds |
Employees working on the top level of roof greater than 6 foot fall without adequate fall protection.
Cross braces are not installed at all locations creating a possible stability hazard on this tubular welded scaffold
|
Fall Protection |
1926.501(b)(1)or (13)
1926.451(c)(1)
|
Employer needs to provide fall protection to employees at all working levels and the fall distance needs to be limited to 6 foot fall distance. Reference 1926.502 for Fall protection systems and criteria and practices.
Provide cross bracing at all locations where the horizontal members support the outer and inner legs. See manufacturer's guidelines.
|
VIEW
|
Scaffolds |
Employer needs to provide fall protection to employees at all working levels and the fall distance needs to be limited to 6 foot fall distance. Reference 1926.502 for Fall protection systems and criteria and practices.
Provide cross bracing at all locations where the horizontal members support the outer and inner legs. See manufacturer's guidelines.
|
Fall Protection |
1926.451(f)(6)
|
The scaffold should not be erected, dismantlled, used or altered near energized powerlines.
|
VIEW
|
Scaffolds |
This scaffold was within 10 feet of the overhead powerline with 300 volts to 50KV.
|
Fall Protection |
1926.451(f)(6)
|
The scaffold should not be erected, dismantlled, used or altered near energized powerlines |