Electrical |
Spray rig for styrene and MEKP not grounded to prevent static buildup |
Electrocution |
1910.107(c)(9)
|
Employer installed grounding system as per manufacturer's instruction.
|
VIEW
|
Electrical |
Spray rig for styrene and MEKP not grounded to prevent static buildup |
Electrocution |
1910.107(c)(9)
|
Employer installed grounding system as per manufacturer's instruction
|
VIEW
|
Electrical |
Employer had modified a 220V receptacle by attaching a 110V outlet; outlet also had knockouts missing.
|
Electrocution |
1910.305(b)(1) and 303(b)(2)
|
Entire receptacle replaced and installed per UL
|
VIEW
|
Electrical |
Continuous path to ground not maintained; multiple cords used for fixed equipment.
|
Electrocution |
1910.304(f)(4) and 305(g)(1)(iii)
|
Fixed wiring installed where applicable
|
VIEW
|
Electrical |
Exposed live parts. Duplex receptacle with exposed and energized contacts.Duplex receptacle missing faceplate |
Electrocution |
1910.303(g)(2)(i) and 1910.305(b)(2)
|
Electrical receptacle should be properly installed and fixed into position in accordance with NEC.
|