MAIN

8  Photos found for the Fire category.

  Category Description Hazard Standard Corrective Action
VIEW Fire Hazard: Acetylene and oxygen cylinders stored together Burned 1910.253(b)(4)(iii) Separate the cylinders while in storage a minimum distance of 20 ft. or by a non combustible barrier at least 5 ft. high having a fire resistance rating of at least 1/2 hour.
VIEW Fire Hazard: This is a photo of oxygen and acetylene cylinders not being properly stored. Burned 29 CFR 1910.253(b)(4)(iii Separate the cylinders 20 feet apart or provide a barrier with a fire rating of at least one half hour.
VIEW Fire Unlabeled diesel tank unlabeled storage tank 1910.1200(f)(5)(i) Place label on tank


PREV
 
Showing records 6 - 8 of 8.