Category
|
Description
|
Hazard
|
Standard
|
Corrective Action
|
VIEW
|
Electrical |
Plug with missing ground. |
Ground plug missing. |
1910.304(f)(4). |
Replace plug |
VIEW
|
Electrical |
Electrical euipment, the cord, was not free from a recognized hazard, the flexible cord's outer insulation was damaged exposing the inner cords. |
electrocution |
1926.403(b)(1) |
Replace cord with approved fully insulated cord. |
VIEW
|
Electrical |
This is a photo of a box enclosing a disconnect that was used in a sawmill. |
Fire |
1910.305(b)(i) |
Provide plugs for the knockout holes left open. |
VIEW
|
Electrical |
The employer had moved the controls for a gang saw. The employer had never provided any strain relief on the flexcord. |
Electrocution |
1910.305(g)(2)(iii) |
Provide straing relief at both ends of the flex cord connecting the controler to the saw. |
VIEW
|
Electrical |
Cables with splices within 10 feet of the holder were used. |
Contact with live parts. |
1910.254(d)(8) |
Defective cable removed and replaced. |